| Application: | Refrigerated And Deep Freeze Doorways, Cold Store Air Locks | Base Fabric: | 100% Polyester, Two Layer Multifilament (DIN EN ISO 2076) |
|---|---|---|---|
| Total Weight: | 3700 G/m² / 109 Oz/yd² (DIN EN ISO 2286-2) | Thickness: | 3.10 Mm / 122 Milli-inch (DIN EN ISO 2286-3) |
| Cold Resistance: | -30 °C / -22 °F (DIN EN 1876-1) | Heat Resistance: | +70 °C / +158 °F (N-O-PA-1057) |
| Tensile Strength Warp/Weft: | 8000/7000 N/5 Cm / 914/799 Lbf/inch (DIN EN ISO 1421.1) | Tear Resistance Warp/Weft: | 1200/1000 N / 270/225 Lbf (DIN 53363) |
| Coating Adhesion: | 180 N/5 Cm / 221 Lbf/inch (DIN EN ISO 2411) | Flame Retardancy: | Max. 100 Mm/min / 3.9 Inch/min (DIN 75200) |
| Strip Width: | 200 Mm / 300 Mm Standard, Other Widths Cut To Order | Surface: | Unlacquered PVC, Matt Embossed, Anti-UV Stabilised |
| Highlight: | Freezer Grade PVC Strip Curtain,Anti-UV Cold Room Curtain,Low Temperature Door Belt |
||
A cold room curtain is judged on one number: the temperature at which it stops folding. Ordinary strip compounds stiffen around −15 °C and begin to craze along the hook line, so the first pallet truck of the shift breaks a strip that looked perfect the night before. This 3.10 mm belt is compounded for −30 °C, which means it still drapes against the frame with the store at deep freeze and still recovers its shape after a forklift shoulder pushes through it.
It is a 3700 g/m² PVC coated polyester belt (109 oz/yd²) built on a two-layer multifilament base, supplied either as cut strips or as a continuous sheet trimmed to the door width. The skin is unlacquered and matt embossed, and the embossing is not cosmetic: a smooth face bonds frost into a glassy film that welds neighbouring strips together, while the embossed face releases it.
Customized Color is available.
Yellow, black, green color, etc.
Flame retardant and cold resistant characteristics are available.
Freezer Duty CompoundThe plasticiser system decides whether a curtain survives in a freezer. A standard phthalate load gives good flexibility at room temperature and glass transition well above freezer conditions, so strips hang like boards, crack at the suspension holes and shed fragments onto the floor. Our compound is formulated for cold flexure and verified to DIN EN 1876-1 at −30 °C (−22 °F); the same formulation keeps a heat resistance of +70 °C, so a strip that has hung in the cold store all winter can be steam washed or moved to a warm dock without deforming.
Ultraviolet stabilisation sounds irrelevant inside a dark cold room, and it would be if the door stayed shut. In practice refrigerated warehouses open to the yard for hours in summer, and the doorway strips take low angle sun at exactly the angle that ages PVC fastest. The anti-UV package holds colour and elongation through that exposure, which is why the curtain is not replaced every second summer, and why the cold flexibility it had on day one is still there in year three.
Strip Data and Field Meaning| Property | Value | What it changes on site |
|---|---|---|
| Substrate | 100% polyester, two layer multifilament | Load is carried by the weave, not the coating, so strips do not neck at the hooks |
| Grammage | 3700 g/m² (109 oz/yd²), DIN EN ISO 2286-2 | Mass keeps strips hanging plumb in draught from the freezer fans |
| Gauge | 3.10 mm (122 milli-inch), DIN EN ISO 2286-3 | Sacrificial wear depth at the forklift fork line |
| Cold flex limit | −30 °C, DIN EN 1876-1 | No cracking when the door is cycled at deep freeze |
| Heat limit | +70 °C, N-O-PA-1057 | Survives washdown and summer loading without sagging |
| Tensile, warp and weft | 8000/7000 N/5 cm, DIN EN ISO 1421.1 | Strips stay in the doorway when a trailer curtain or cage trolley catches them |
| Tear, warp and weft | 1200/1000 N, DIN 53363 | A fork puncture stays local instead of running the full drop |
| Peel bond | 180 N/5 cm, DIN EN ISO 2411 | No skin lift around punched holes and clamp bars |
| Burn rate | Max. 100 mm/min, DIN 75200 | Supports fire documentation for the hall, not just the freezer |
| Strip widths | 200 mm and 300 mm standard, others cut to order | Matches the overlap the door width actually needs |
![]()
![]()
![]()
![]()
Infiltration through an unprotected freezer doorway is the largest single refrigeration load on most cold stores. Overlapping strips in a flexible compound cut that exchange to a fraction, and the tear and adhesion values above are what keep the overlap intact over a season of abuse; a stiff curtain that has split at the top looks installed but seals nothing. Because strips are individually replaceable, maintenance becomes a matter of swapping one drop rather than re-hanging the whole doorway, which is the difference between a half hour job and a closed bay.
Supply, Spares and AssuranceWe supply full rolls for door manufacturers, pre-cut strip sets with punched suspension holes, and complete curtain kits with rail and hooks. Every batch is sampled for mass, gauge, tensile and low temperature flex, and the retained sample is kept for a year so that a warranty question can be answered from the record rather than from recollection. Reports to DIN EN 1876-1, DIN EN ISO 1421.1 and DIN 75200 travel with the shipping documents when they are asked for. Where the cold room opens straight onto a yard, pair this curtain with our 3700 g/m² anti-UV dock shelter belt, which is the front curtain grade of the same family.